How to Properly Test a Fire Alarm Call Point: A Step-by-Step Guide
How to Test a Fire Alarm Call Point
Ensuring that your fire alarm call points are in full working order is critical for maintaining fire safety within any building. As a fire and security company operating in the South West of England, ELECSEC understands the importance of thorough testing and maintenance. In this blog post, we will provide a step-by-step guide on how to test a fire alarm call point, ensuring that it meets all regulatory and safety requirements.
What is a Fire Alarm Call Point?
A fire alarm call point, or a manual call point, is an essential component of a fire alarm system. It allows individuals to manually trigger the fire alarm if they detect a fire or an emergency, alerting building occupants and emergency services. Fire alarm call points are typically located near exits and high-traffic areas to make them easily accessible, and they are bright red to easily catch the attention of those in the building.
Common fire alarm call points include break-glass call points, with a glass cover that must be broken to trigger the alarm, and non-break-glass call points, without the glass and just a button to activate the alarm.
Why Regular Testing is Important
Mechanical components can degrade over time, electric components can become faulty, and your fire alarm call point could become damaged, affecting the dependability. Therefore, regular testing of fire alarm call points is essential to ensure their reliability in an emergency.
Regular testing will ensure that all these are checked and that your building complies with the British Standards for fire alarm systems, such as BS 5839-1:2017, which mandates that fire alarm systems, including call points, be regularly tested and maintained.
Without testing, faults or malfunctions can go unnoticed, compromising the safety of your building, breaching legal compliance and potentially invalidating your insurance cover.
It’s also important to remember that weekly testing is not the same as your fire drills. Fire alarm testing covers the health and response of your alarm system, whereas fire drills test you and those within your building, and your ability to carry out an evacuation in the event of a fire.
Arrange a Free Site Survey
Contact us today on 0117 978 0775 and speak to our expert team for a quote.
Safety Precautions Before Testing
Notify relevant personnel: Notify building occupants and management that a fire alarm test will take place to prevent unnecessary confusion and evacuations.
Isolate the alarm system: Check that the alarm control panel is connected to the Alarm Receiving Centre and it is in test mode. This ensures the test does not trigger alarms across the entire building or alert the fire brigade.
Have testing equipment ready: Have the manual call point key or testing tool with you. This will be needed to reset the system. It’s also handy to have any necessary documentation for recording test results.
Tools Needed For Testing
Step-by-Step Guide to Testing a Fire Alarm Call Point
1. Identify the Call Points to Test
First, identify which call points need to be tested. It is recommended that different call points be tested on a rotating basis so that all devices in the building are tested over time. Typically, a selection of call points should be tested weekly, ensuring comprehensive system coverage.
2. Use a Call Point Test Key
To avoid damaging the call point or triggering a glass break unnecessarily, use a call point test key. Most fire alarm call points have a slot for a special test key or test tool, which simulates activation without breaking the glass. Insert the key into the designated slot, and gently press to simulate a fire alarm activation.
If the call point does not have a test key mechanism, or if a physical test of the glass is required, use a resettable call point or replacement glass to perform the test.
3. Observe the Alarm Activation
Once the test key or tool is used, observe the response of the fire alarm system. The fire alarm control panel should receive a signal indicating that the call point has been activated. In test mode, the system should log the activation without triggering a full evacuation.
Check the fire alarm control panel for any errors or faults. If the system fails to register the activation, or if an error is displayed, further investigation may be required to determine if the call point or the system has a fault.
4. Record the Test Results
Once the call point has been successfully tested, record the results. Document which call points were tested, the time and date of the test, and whether the call point activated as expected. If any faults were detected, they should be noted for immediate or scheduled repair.
Maintaining an accurate log of all tests is critical for compliance with fire safety regulations and for identifying any recurring issues with the system.
5. Reset the Call Point and Fire Alarm System
After testing, the fire alarm call point and system must be reset. If the glass was broken as part of the test, it will need to be replaced with a new one. Alternatively, if a resettable call point was used, follow the manufacturer’s instructions to reset the mechanism.
Next, reset the fire alarm control panel. Ensure that the system is fully operational and that the call point is no longer showing as activated. If the fire alarm was placed in test mode, ensure it is returned to normal operating mode to re-enable the full alarm system.
Common Issues During Testing
No signal received at the control panel: If the fire alarm control panel does not register the activation of the call point, there may be an issue with the wiring or the call point itself. In such cases, a qualified technician should investigate the cause.
Faulty glass or mechanism: In some cases, the glass or activation mechanism of the call point may be damaged or faulty. This should be replaced immediately to ensure the device is ready for future use.
False activations: Sometimes, call points can be accidentally triggered due to damage or vandalism. Regular testing helps identify such call points so they can be repaired or replaced.
Failure to reset the call point: If the call point is not properly reset after activation using the correct key or tool, it can remain non-functional or show as faulty on the control panel.
Call point not activating: A call point may fail to trigger the alarm panel due to internal faults, wiring issues, or a buildup of dust and debris. Should this occur, a trained technician should investigate this.

How Often Should Fire Alarm Call Points Be Tested?
Fire alarm systems including manual call points, should be tested regularly. Weekly testing is recommended for most commercial properties, and each week, a different call point should be tested to ensure comprehensive system coverage over time.
A professional fire alarm maintenance company should conduct more thorough inspections at least once a year, which should include testing all call points, detectors, and the fire alarm control panel.
Failure to regularly test and maintain fire alarm systems, including call points, can result in fines or legal action, especially if a fault in the system leads to a delay in emergency response during a fire.
Who Should Conduct Fire Alarm Call Point Testing?
A responsible person is legally required to ensure that fire alarm call point testing is carried out. This ‘responsible person’ will typically be the building owner, employer or a designated manager.
The designated responsible person should do weekly testing, whereas professional engineers should carry out annual inspections and maintenance.
What Should You Do If A Call Point Fails?
Should a fire alarm call point malfunction, you must report the issue to your fire alarm maintenance company and, if the occupants are at risk, evacuate the building. This issue should also be logged in the fire logbook with details of the fault and how it was resolved.
Ensuring Regular Fire Alarm Maintenance
Testing fire alarm call points is a critical aspect of fire safety management. Regular testing ensures that the call points will function as intended in the event of an emergency and helps to maintain compliance with fire safety regulations.
Here at Elecsec, we understand the importance of proper fire alarm maintenance. If you’re based in Bristol or the South West of England and need assistance with your fire alarm system, our team of professionals is here to help. With over 50 years of combined experience in installing Fire and Security Systems, we offer comprehensive fire alarm testing, maintenance, and installation services to keep your premises safe and compliant.
For all your Fire and Security needs contact our expert team today on 0117 978 0775.
Lastly, to keep up with all of our news and to find some inspiration, you can follow us on Instagram and Facebook.