Fire alarm panel - AI - Elecsec

A Guide to Fire Alarm Testing For Business Owners

If you are responsible for a commercial business then you have the legal duty to ensure your building is safe for your employees and customers and that you adhere to all health and safety policies and procedures, including fire alarm testing.

It is a legal requirement to carry out regular fire alarm tests and fire risk assessments to ensure your department has the correct equipment in place such as fire extinguishers and working fire alarm call points and that all fire exits are accessible at all times.

Failing to carry out regular testing and risk assessments in your department, can lead to potential loss of lives, heavy fines and imprisonment. It is important to adhere to all policies and procedures to keep not only yourself safe but also your employees and customers.

What Does The Law Require For Fire Alarm Testing?

Often, the lines blur between the law, which tells you what you are responsible for, and the British Standard, which is the accepted way to show that you have met your responsibilities.

The Regulatory Reform (Fire Safety) Order 2005

In England and Wales, the Regulatory Reform (Fire Safety) Order 2005 legally governs fire alarm testing and safety. This is the main fire safety law for businesses, and it applies to almost all non-domestic premises and communal areas of residential buildings.
Under this Order, the “responsible person” (typically the employer, owner or whoever controls the premises) must carry out a fire risk assessment and put suitable fire precautions in place. They must also ensure that their fire alarm systems are regularly maintained and tested to keep them in efficient working order and good repair.
A competent person must carry out this testing and should follow the manufacturer’s instructions and relevant British Standards, such as BS 5839-1:2025.
The Order does not state specific testing dates, yet it sets the duty and leaves you to show that you have met it. Serious breaches can lead to unlimited fines and, in the most serious cases, imprisonment.

BS 5839-1:2025

BS 5839-1:2025 is the British Standard code of practice for fire detection and fire alarm systems in non-domestic buildings. The 2025 edition came into effect on 30 April 2025, replacing the 2017 edition.
As it is a code of practice, BS 5839-1 uses the word ‘should’ rather than ‘must’. In practice, though, it is the benchmark that fire and rescue services, insurers and courts use to judge whether a system has been properly maintained.
Failure to comply with BS 5839-1:2025 does not break the law on its own, but you may struggle to defend your safety choices in court, and you may fail audits that can result in official delays or complete building shutdowns.

Section 156 of the Building Safety Act 2022

Since 1 October 2023, section 156 has strengthened the Fire Safety Order in both England and Wales.
This means all Responsible Persons legally must record complete fire risk assessments and fire safety arrangements in writing, regardless of business size or staff numbers.
The old exemption for businesses with fewer than five employees no longer applies. You must record fire risk assessments and fire safety management arrangements in full, not just significant findings, including the specific name and organisation of the individual responsible for conducting or reviewing the fire risk assessment. You must also record fire safety arrangements such as how you organise, control, monitor and review your fire precautions.
If you use someone else to carry out or review your fire risk assessment, you must record their name and, where relevant, their organisation.
Should you choose to hand over responsibility for a building, you must ensure you have passed on the relevant fire safety information to the incoming Responsible Person.

Mixed-use Buildings: The Fire Safety Act 2021 and Related Regulations

If your business operates in a building that also contains two or more homes, such as a shop with flats above, extra rules apply.
The Fire Safety Act 2021 confirms that the Fire Safety Order covers the building’s structure, external walls including cladding, windows and balconies, and the entrance doors to individual flats. Therefore, you must consider these in your fire risk assessment.
In England, the Fire Safety (England) Regulations 2022 add further duties in these buildings, including regular checks of fire doors in buildings over 11 metres tall.

Recent Changes To Be Aware Of in 2026

Residential Evacuation Plans (England, from 6 April 2026)

The Fire Safety (Residential Evacuation Plans) (England) Regulations 2025 now apply to residential buildings with two or more homes that are at least 18 metres or seven storeys tall, or over 11 metres tall with a simultaneous evacuation strategy.
Responsible Persons must make reasonable efforts to identify residents who may require additional support in evacuation, offer them a bespoke fire risk assessment and put reasonable proportionate measures in place.
Most business owners won’t be affected by this. If you are the Responsible Person for a large mixed-use building, check whether it applies to you.

Fire Risk Assessor Certification (England, proposed)

In March 2026, the government launched a consultation on making it mandatory for fire risk assessors to have certification in response to the Grenfell Tower Inquiry.
A national competence standard, BS 8674:2025, already exists; however, this is not yet law.

Frequency of Testing and Equipment and Call Points Testing

Fire alarm testing is an integral part of ensuring the safety and compliance of any building, as it guarantees that systems are functioning properly in the event of an emergency. Fire alarm testing should be carried out on a weekly basis by an appointed person such as a manager or experienced member of the team.

Before you complete a fire alarm test it is important to notify your building occupants so they know it is only a test and do not need to leave the department. Having the fire alarm test set for the same day each week and at the same time is recommended as it helps everyone become familiar with the weekly test procedure.

The physical test involves activating a call point to trigger the fire alarm and checking that it sounds and resets as expected. The results of these tests should be recorded in a fire safety logbook as part of the property’s fire safety maintenance records.

Testing the fire alarm call point must be done with the specific equipment provided and all staff who carry out a test must be trained adequately to ensure they carry out the test correctly. Regular checks should also be completed on all equipment such as the fire extinguishers, fire blankets and checking all fire exits for any barriers.

What BS 5839-1:2025 Recommends

Below, we have compiled what BS 5839-1:2025 recommends for a fire alarm testing routine; however, your fire risk assessment may require more, depending on your premises.
WhenAction
Daily
  • Check that the fire alarm control panel shows normal operation with no fault or disablement lights showing.
  • Record any faults in your fire logbook and report them to your maintenance company immediately.
Weekly
  • Test the system using a manual call point during normal working hours. Ideally, do this on the same day and at the same time each week, using a different call point each time so that each is tested in rotation.
  • Check that the sounders and visual alarms operate, and that anything linked to the alarm works as it should, such as door hold-open devices releasing.
  • Record the test, including which call point you used, in the logbook.
Every six months
  • Call in a competent fire alarm engineer to inspect and service the system. Note: the 2025 edition allows a tolerance of one month either side of each six-month interval, counted from the date the system was accepted. Therefore, a service between five and seven months after the last is still in line with the standards.
  • At every service visit, the engineer must check and adjust the control panel’s clock for accurate event logs.
  • Where the system is linked to an alarm receiving centre, test that each alarm type is received correctly.
Every twelve months
  • Test every detector, call point and interface over 12 months.

Records and Documentation

BS 5839-1:2025 puts more emphasis on paperwork, and so do fire safety inspectors. Make sure that you have an up-to-date logbook recording weekly tests, false alarms, faults and service visits.
You should also have a cause-and-effect matrix, or a similar description, explaining what the system does when each device operates. Provide this at handover as per the 2025 edition.
Record any variations from the standard in your logbook, and obtain a modification certificate whenever you extend or alter the system.

Access and Security

Ensure all system interfaces, such as lift overrides and fire door controls, remain fully accessible for testing. Concealed or obstructed panels are no longer acceptable.
In the 2025 edition, strict controls have been introduced for remote access security to fire alarm systems, using defined transmission speeds, cybersecurity protocols, and mandatory on-site labelling. Therefore, consult your maintenance company for further guidance on how remote connections to your panel are controlled.
Fire alarm panel - AI - Elecsec

Having a Dedicated Fire Marshall in Department

Choosing a dedicated fire marshal in a department is an important step in enhancing workplace safety. The fire marshal’s role will include overseeing all fire safety procedures, ensuring that staff are trained in emergency evacuations and also regularly checking fire safety equipment.
By designating a specific individual to take on this responsibility, a department ensures that there is always someone on hand to manage fire-related incidents and to lead colleagues during drills or in the event of an actual emergency. This proactive approach helps create a safer work environment and ensures compliance with fire safety regulations.

Health and Safety Fire Training

Fire alarm testing is a very important aspect of health and safety training for staff, ensuring that employees understand how to properly use and respond to fire alarm systems in the workplace. Training should cover the procedures for activating alarms, evacuating the building safely and recognising the different alarm signals.
It is important that staff are familiar with regular fire alarm testing schedules and know how to identify potential issues with the system itself, such as false alarms or any faults. By providing this training, employers can ensure that staff are prepared to act quickly and safely in the event of a fire emergency.

How to Complete a Fire Alarm Test

All tests should be carried out as advised by the department fire safety manager, there are simple steps that need to be followed to ensure that the test is completed safely, efficiently and correctly.
  • Notify Everyone: Start by informing all staff and anyone in the building that you’ll be carrying out a fire alarm test. This avoids confusion or unnecessary evacuations.
  • Contact Monitoring Services: If your system is linked to an external service, let them know you will be completing a test, so they don’t send out the fire brigade unnecessarily.
  • Trigger the Alarm: Use a manual call point with a test key, or the break-glass unit, to activate the system. Pick a different call point each time to ensure full coverage of the department.
  • Check the Alarm: Walk around the building and confirm that all sounders and visual indicators are working properly across the building.
  • Review the Fire Alarm Panel: Make sure the fire alarm panel correctly shows the activated zone and if any faults have appeared.
  • Reset the System: Once the test is completed, reset the alarm system at the control panel to clear it.
  • Log the Test: Record what you did, the time, date, and any issues found in the fire safety logbook.
  • Confirm Normal Operation: Finally, let staff and any monitoring services know that the test is complete and the system is back to normal.
These steps ensure your fire alarms are working correctly and are fully compliant with fire safety regulations.

Why choose Elecsec for Fire and Security Systems?

Elecsec specialises in the system design, installation, commissioning and maintenance of a wide range of fire protection systems for commercial and retail premises in Bristol and beyond. For all your Fire and Security needs, our team are available to help.

If you need to speak to one of our experts about installing a fire alarm system in your commercial property or need some advice, simply call 0117 978 0775 or contact our friendly team via our online form.